ELEC-01Low-voltage wiring

Voltage Drop Calculator

Calculates voltage drop on copper cable with a simplified resistance method and finds the smallest standard cross-section that stays within the IEC 60364-5-52 limits.

V

Changing the system fills in a typical value.

A
m

One-way length from the distribution board to the load.

Formula

This simplified method ignores cable reactance and power factor and uses conductor resistance only. Length L is in m, current I in A and cross-section A in mm².

Single-phase 2-wire                    e = 35.6 · L · I / (1000 · A)
Three-phase 3-wire                     e = 30.8 · L · I / (1000 · A)
Single-phase 3-wire, three-phase 4-wire e = 17.8 · L · I / (1000 · A)

Voltage drop % = e / reference voltage × 100

The coefficients come from the resistivity of annealed copper (1/58 Ω·mm²/m) with conductivity derated to 97 % for practical conductors: 1,000 ÷ (58 × 0.97) ≈ 17.8. A single-phase 2-wire circuit has two conductors in the loop, which gives 35.6, and a three-phase 3-wire circuit uses √3, which gives 30.8. The calculator derives the coefficients the same way, and automated tests check that they match these three values.

For single-phase 3-wire and three-phase 4-wire systems, e is the drop between one line and neutral, so the percentage uses the line-to-neutral voltage. For a 380/220 V three-phase 4-wire system, use 220 V.

Permitted voltage drop

IEC 60364-5-52 Annex G recommends limiting the voltage drop between the origin of the installation and the equipment to the values below. Korea adopts the same values in KEC 232.3.9.

Installation typeLighting (%)Other uses (%)
A: supplied directly from a public low-voltage network35
B: supplied from a private supply (own transformer)68

Where the wiring is longer than 100 m, the limits may be increased by 0.005 % for each metre beyond 100 m, up to 0.5 %. The calculator applies this automatically. National wiring rules can differ, so check the rules where you work.

Worked example

Single-phase 220 V, 20 A load, 50 m run, 4 mm² copper, lighting circuit on a public low-voltage supply:

The calculator opens with these values.